RCM 01 2018-01-10T18:52:36+00:00

EnCell™ Battery Cell Monitor

Multiple Cell Monitor with Impedance and Current Monitoring

Product Specifications

  • NERC PRC-005-6 compliant
  • For use with 2 – 15V Ni-Cad or lead Acid batteries
  • Communication via 900 mHZ radio frequency to EnCell™ Gateway or EnCharge Pro battery charger
  • Operating temperature -40° to +70° C (-40° to +158° F) (0-95% non-condensing humidity)
  • Two year warranty
Battery-Cell-Monitor_ICM

Features

  • Monitors & records voltage and temperature of each individual battery cell
  • If voltage temperature is outside a predetermined level, an alarm will be sent to alert appropriate personnel

Benefits

  • Identify a failing battery cell before it starts to deteriorate other cells in the string
  • Asset tracking for planning purposes, as well as warranty claims
  • No need to utilize a voltage meter to check battery voltages on a periodic basis as they are recorded with the battery cell monitor

Remote Capabilities

This product is compatible with EnVision Remote Monitoring – a cloud hosted solution, allowing convenient access to the status of equipment and data, anywhere at anytime.

  • Allows convenient real-time access to the status of equipment and data
  • Allows viewing of historical data and uses information to determine bad or deteriorating cells
  • Status page shows current status of faults, fault count readings and settings
  • Provides notifications when conditions are out of compliance
ModelCell VoltageSupply VoltageMonitoring Accuracy
(per battery cell)
Physical Dimensions
WxHxD (in inches)
Cell Current Draw
RCM01E021-4 VDC9.0 - 36.0 VDC±5mV6.00 x 2.00 x 2.00.25-.75mA
RCM01E125-15 VDC9.0 - 36.0 VDC±10mV6.00 x 2.00 x 2.00.10 - .50 mA
RCM01C021-4 VDC1.0 - 4.0 VDC±5mV4.00 x 2.00 x 1.25100 - 300 mA
RCM01C125-15 VDC5.0 - 15.0 VDC±10mV4.00 x 2.00 x 1.2515 - 50 mA